Sonel Test Measurement MIC-5010

Sonel Test Measurement MIC-5010

0 out of 5

$1,334.00

SKU: MIC-5010 Category: Tags: , , ,
View cart

Description

The MIC-5010 is a portable, rugged, easy-to-use, 5 kV class insulation test meter. The MIC-5010 has a wide measurement range, selectable test voltages, and excellent safety features.

  • Measurement to 15 TΩ
  • User-selectable test voltage any from 50 to 1,000 V (with 10 V resolution) and 1,000 to 5,000 V (with 25 V resolution)
  • Continuous indication of measured insulation resistance or leakage current
  • Audio beeps every five-second periods to indicate measurement progress
  • Indication of actual test voltage during measurement
  • 1.2 mA and 3 mA test current
  • Step voltage insulation resistance measurement (SV)
  • Selectable test times (T1, T2 , T3 from 1 to 600 seconds) to measure one or two absorption coefficients
  • Adjustable measuring time to 99 59’
  • Polarization index (PI) and dielectric absorption ratio (DAR) measurements
  • Dielectric Discharge calculation (DD)
  • High-noise immunity, digital filters function for measurements in high noise environment (10 s, 30 s , 60 s)
  • Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557-4
  • Adjustable limits for measured resistance RISO and RCONT
  • Measurement of capacitance during the measurement of RISO
  • DC and AC voltage measurement in the range of 0 to 600 V
  • Meter conforms to EN 61557

>

Safety First Features:

  • CAT-IV 600V, CAT-III 1000V
  • Automatic discharge of tested object after the insulation resistance measurement completes to remove high-voltage charge remaining due to cable capacitance
  • Protection against measuring live objects, measurement will not proceed
  • Measurements with test leads up to 66 ft / 20 m length

>

Construction:

  • Backlit keyboard and display
  • Rugged IP 54 case Protected from water spray from any direction
  • Power supply from battery packs, low battery warning indicator, built-in fast charger

>

Memory Features:

  • 990 cells of memory (11,880 records) to save test results
  • Data transmission to a PC via USB cable